Start typing to search LMXFORGE...
// Articles, calculators, products, and database: 36 pages indexed
// POWER DISTRIBUTION

MV/LV Distribution Design: Feeder Sizing, Fault Levels, and Selectivity

June 2026 Updated October 2026 10 min read

What Is a Distribution System?

An electrical distribution system is the network of conductors, switchgear, transformers, and protective devices that delivers power from the utility supply or generation source to individual loads. It spans two voltage tiers: medium voltage (MV), typically above 1 kV up to roughly 35 kV (IEC MV equipment standards extend to 52 kV), and low voltage (LV), typically below 1kV (most commonly 480V in North America, 415V or 400V in IEC jurisdictions).

Distribution design is one of the most consequential engineering disciplines in a project. The decisions made at this stage, how many transformers, what impedance, which feeder sizes, how protection is coordinated, directly affect capital cost, operational reliability, and safety for the life of the facility.

System Architecture

Most industrial and commercial distribution systems follow a recognizable hierarchy:

Redundancy is designed into the architecture at the transformer level (N+1 or 2N configurations) or at the bus level (bus section breakers with auto-changeover schemes). The appropriate level depends on the facility criticality and owner requirements.

Feeder Sizing: The Three Checks

Every feeder in the distribution system, MV or LV, must satisfy three independent sizing criteria. All three must pass; the largest resulting conductor size governs.

In practice, ampacity governs for most LV feeders. Short-circuit withstand governs when fault levels are very high (near the transformer secondary) or protection clearing times are long. Voltage drop governs for long cable runs, particularly motor feeders in large plant layouts.

Fault Level Calculations

The available fault current at any point in the distribution system must be calculated to:

The fault level decreases as you move downstream from the source: impedance of cables, transformers, and bus reduces the available current at each node. In a radial LV system the highest fault level is normally at the transformer secondary terminals (the main LV bus), where only the transformer and source impedance limit the fault current. Motors and on-site generation can raise it, and the MV bus upstream has its own fault level.

For a distribution transformer, the three-phase fault current at the LV terminals is approximately:

A 1000kVA, 480V transformer with 5.75% impedance produces approximately 20.9kA of three-phase fault current at the secondary terminals, assuming an infinite source (utility impedance and motor contribution are ignored). This is the starting point for all downstream fault level calculations.

Selectivity (Discrimination)

Selectivity, called discrimination in IEC terminology, is the ability of a protection system to isolate only the faulted section of the network while leaving the rest of the system energized. A properly selective system means a fault on a sub-board feeder trips only the sub-board incomer, not the main LV switchboard breaker.

There are three main selectivity methods:

Full selectivity (total discrimination) means no upstream device trips for any downstream fault. Partial selectivity means selectivity is achieved up to a certain fault current level: above which both devices may trip simultaneously.

Cable Derating in Distribution Design

Distribution feeders are rarely installed in isolation. MV feeders share cable trenches; LV feeders share cable trays or conduit banks. Grouping reduces the ampacity of each cable, and this must be accounted for in feeder sizing.

Key derating factors to apply:

Some designers also size feeders at about 80% of the derated ampacity (a 0.8 utilization factor) to allow for future load growth; this is a project practice, not a code rule. Separately, the NEC requires continuous loads to be sized at 125% in most feeder and branch-circuit cases.

Where Standards Diverge

Common Design Pitfalls

Summary

// RELATED CALCULATORS

Short Circuit & Voltage Drop Calculators

Calculate fault current at the transformer secondary using the MVA method, and check voltage drop on feeders: free, browser-based, NEC and IEC methods.

// RELATED TOOL

CableSched-LMX

Excel-based cable schedule generator: automates ampacity checks, voltage drop across all feeders, and routing references at project scale. Coming Soon.

Disclaimer: This guide is for general information and preliminary reference only. Engineering judgment is required. Verify methods, values, and code requirements against the edition adopted for your project, the project specification, and manufacturer data before use in design documents.

Found an error or an outdated reference? Let us know at [email protected].

← Back to Articles