// POWER DISTRIBUTION

MV/LV Distribution Design — Feeder Sizing, Fault Levels, and Selectivity

June 2026 10 min read LMXFORGE

What Is a Distribution System?

An electrical distribution system is the network of conductors, switchgear, transformers, and protective devices that delivers power from the utility supply or generation source to individual loads. It spans two voltage tiers — medium voltage (MV), typically 1kV to 36kV, and low voltage (LV), typically below 1kV (most commonly 480V in North America, 415V or 400V in IEC jurisdictions).

Distribution design is one of the most consequential engineering disciplines in a project. The decisions made at this stage — how many transformers, what impedance, which feeder sizes, how protection is coordinated — directly affect capital cost, operational reliability, and safety for the life of the facility.

System Architecture

Most industrial and commercial distribution systems follow a recognizable hierarchy:

Redundancy is designed into the architecture at the transformer level (N+1 or 2N configurations) or at the bus level (bus section breakers with auto-changeover schemes). The appropriate level depends on the facility criticality and owner requirements.

Feeder Sizing — The Three Checks

Every feeder in the distribution system — MV or LV — must satisfy three independent sizing criteria. All three must pass; the largest resulting conductor size governs.

In practice, ampacity governs for most LV feeders. Short-circuit withstand governs when fault levels are very high (near the transformer secondary) or protection clearing times are long. Voltage drop governs for long cable runs — particularly motor feeders in large plant layouts.

Fault Level Calculations

The available fault current at any point in the distribution system must be calculated to:

The fault level decreases as you move downstream from the source — impedance of cables, transformers, and bus reduces the available current at each node. The highest fault level in a system is always at the transformer secondary terminals, where only the transformer impedance limits the fault current.

For a distribution transformer, the three-phase fault current at the LV terminals is approximately:

A 1000kVA, 480V transformer with 5.75% impedance produces approximately 20.9kA of three-phase fault current at the secondary terminals. This is the starting point for all downstream fault level calculations.

Selectivity (Discrimination)

Selectivity — called discrimination in IEC terminology — is the ability of a protection system to isolate only the faulted section of the network while leaving the rest of the system energized. A properly selective system means a fault on a sub-board feeder trips only the sub-board incomer, not the main LV switchboard breaker.

There are three main selectivity methods:

Full selectivity (total discrimination) means no upstream device trips for any downstream fault. Partial selectivity means selectivity is achieved up to a certain fault current level — above which both devices may trip simultaneously.

Cable Derating in Distribution Design

Distribution feeders are rarely installed in isolation. MV feeders share cable trenches; LV feeders share cable trays or conduit banks. Grouping reduces the ampacity of each cable, and this must be accounted for in feeder sizing.

Key derating factors to apply:

It is common in distribution design to size feeders at 80% of the derated ampacity (a 0.8 utilization factor) to allow for future load growth without immediate cable replacement.

Where Standards Diverge

Common Design Pitfalls

Summary

// RELATED CALCULATORS

Short Circuit & Voltage Drop Calculators

Calculate fault current at the transformer secondary using the MVA method, and check voltage drop on feeders — free, browser-based, NEC and IEC methods.

// RELATED TOOL

CableSched-LMX

Excel-based cable schedule generator — automates ampacity checks, voltage drop across all feeders, and routing references at project scale. Coming Soon.

← Back to Articles