Start typing to search LMXFORGE...
// Articles, calculators, products, and database: 36 pages indexed
// VOLTAGE DROP

How to Calculate Voltage Drop for LV Cable Runs

June 2026 Updated October 2026 8 min read

Why Voltage Drop Matters

Voltage drop is the reduction in voltage that occurs along the length of a cable carrying current. In a low voltage distribution system, excessive voltage drop means the equipment at the end of the run receives less than its rated supply voltage, leading to reduced motor torque, nuisance tripping of under-voltage relays, dimming of lighting circuits, and potential overheating as motors draw higher current to compensate.

Voltage drop is a sizing criterion that operates independently of ampacity. A cable may be fully adequate to carry the load current thermally (per ampacity derating) while still producing unacceptable voltage drop, particularly on long runs, motor feeders (see motor list for FLC data), and circuits in large industrial plants where equipment can be hundreds of metres from the distribution board.

The Basic Formula

For a resistive load on a three-phase circuit, the line-to-line voltage drop is:

For a single-phase circuit:

Where:

The factor of √3 for three-phase accounts for the phase relationship between conductors. The factor of 2 for single-phase accounts for the return path through the neutral.

For circuits where power factor and reactance are significant (larger conductors, longer runs, or heavily inductive loads), the full phasor formula applies:

Where X is the conductor reactance per unit length and θ is the load power factor angle. For small conductors (roughly below 50 mm² or 1/0 AWG) at power factors above 0.85, the reactance term is small enough that the simplified resistive formula gives adequate accuracy. For larger conductors, include the reactance term. The resistive-only formula is a reasonable, usually conservative estimate for small conductors at high power factor, but it can understate the drop for larger conductors and at low power factor, so include reactance there.

Conductor Resistance Values

Conductor resistance varies with material, cross-section, and temperature. The two most common references are:

A selection of representative copper values. The IEC figures are DC resistance at 20°C from IEC 60228, with the equivalent at 75°C (× 1.216) in brackets; the NEC figures are Table 9 values for the nearest AWG or kcmil size, which is not an exact equivalent of the metric size:

Aluminium conductors have approximately 1.6× the resistance of equivalent copper cross-sections, requiring a larger conductor to achieve the same voltage drop.

Permitted Voltage Drop Limits

Neither NEC nor IEC mandates a single universal voltage drop limit, both give guidance rather than hard requirements, with the expectation that the engineer and project specification define the applicable limit.

Worked Example: Three-Phase Feeder

A 75kW motor at 480V, 0.85 power factor, 0.95 efficiency, is fed from a distribution board 120 metres away. Copper conductor in conduit. Check voltage drop for a 50mm² cable.

For the same motor at 200m, the 50mm² conductor would produce 3.79% drop, over the 3% limit. Stepping up to 70mm² (0.268 Ω/km at 20°C, 0.326 Ω/km at 75°C) gives 2.63%: compliant.

Voltage Drop on Motor Starting

During DOL starting, a motor draws its locked-rotor current (LRA), typically 6–8 times full load current (check the motor datasheet), for a few seconds. This creates a momentary voltage dip that affects not just the starting motor but all loads on the same bus.

The starting voltage drop check uses the same formula with I replaced by ILRA. Because the starting power factor is low (typically 0.2–0.4), the full formula with reactance is more accurate; the resistive-only formula is conservative for small conductors but can understate the drop for large ones. The result must be checked against two criteria:

If the starting voltage drop is excessive, the options are: upsize the feeder cable, change the starting method (star-delta, soft starter, or VFD), or negotiate a lower LRA motor specification with the motor vendor.

Where Standards Diverge

Summary

// RELATED CALCULATOR

Voltage Drop Calculator

Enter equipment rating (kW, kVA, HP, or amps), cable size, and run length: instant voltage drop result with max length at 3% and 5% limits. NEC and IEC methods. Free, browser-based.

// RELATED TOOL

CableSched-LMX

Excel-based cable schedule generator: automates voltage drop checks across all feeders in the project. Coming Soon.

// REFERENCES

Disclaimer: This guide is for general information and preliminary reference only. Engineering judgment is required. Verify methods, values, and code requirements against the edition adopted for your project, the project specification, and manufacturer data before use in design documents.

Found an error or an outdated reference? Let us know at [email protected].